Electrical Cable Size Calculations Best -

Common factors:

| mm² | Current in conduit (A) | Current in air (A) | |-----|------------------------|--------------------| | 1.5 | 15.5 | 19.5 | | 2.5 | 21 | 27 | | 4 | 28 | 37 | | 6 | 36 | 48 | | 10 | 50 | 66 | | 16 | 68 | 88 | electrical cable size calculations

L=80m, I=24.5A, mV/A/m=7.3 [ VD = \frac7.3 \times 24.5 \times 801000 = 14.3 V ] Percentage = (14.3 / 415 = 3.45%) → OK (<5%). Common factors: | mm² | Current in conduit