Short Circuit Current: Rating Calculator __top__

The power supply has 3 kA , which is lower than all others.

Yes. Replace the 3 kA power supply with a 10 kA version, or add a current-limiting fuse (e.g., Class J, 5 kA let-through) ahead of it. Using a fuse with a let-through of 3 kA or less allows the power supply’s rating to be increased per UL 508A SB. short circuit current rating calculator

Panel SCCR = 3 kA (cannot exceed the lowest-rated component). The power supply has 3 kA , which is lower than all others